A simple air conditioner thermostat wired to the EPO switch.
For safety, wire two thermostats in series so BOTH have to trip
before power is shut off.

Note that the EPO rarely does an orderly shutdown, but then this
is a sort of an emergency.
        - Brian


On Mon, May 27, 2019 at 02:00:39PM -0400, Dovid Bender wrote:
Hi,

Is anyone aware of a device that will cut the power if the room goes above X