Re: FreeAxez raised flooring?


From: Owen DeLong <owen () delong com>
Date: Sat, 6 Mar 2010 01:54:00 +0800

Not sure about the purpose of a raised floor if it doesn't create a plenum, but, the
step forward from raised-floor plenum is hot-aisle/cold-aisle which requires a good
bit more discipline in your datacenter, but, is substantially more efficient.

Owen

On Mar 6, 2010, at 12:14 AM, Dorn Hetzel wrote:

What is the purpose of raised flooring if it *doesn't *create a plenum?

On Fri, Mar 5, 2010 at 10:39 AM, Jason Gurtz <jasongurtz () npumail com> wrote:

A consultant has recommended FreeAxez for the raised floor in a new data
center.  I checked it out and have concerns since it says it does NOT
create a plenum and cannot be used as an air handling space; it's a
low-profile flooring system.

How would cooling be done in this scenario?  Open air (with intake/exhaust
mixing) seems like a step backwards in terms of efficiency.

Descriptions of any operation experience with this product will be
gratefully accepted.