Re: "Hypothetical" Datacenter Overheating
From: Lamar Owen <lowen () pari edu>
Date: Mon, 15 Jan 2024 17:56:53 -0500
On Mon, Jan 15, 2024 at 7:14 AM <sronan () ronan-online com> wrote:
I’m more interested in how you lose six chillers all at once.Extreme cold. If the transfer temperature is too low, they can reach a state where the refrigerant liquifies too soon, damaging the
compressor.
Regards, Bill Herrin
Our 70-ton Tranes here have kicked out on 'freeze warning' before; there's a strainer in the water loop at the evaporator that can clog, restricting flow enough to allow freezing to occur if the chiller is actively cooling. It's so strange to have an overheating data center in subzero (F) temps. The flow sensor in the water loop can sometimes get too cold and not register the flow as well. ________________________________
Current thread:
- Re: "Hypothetical" Datacenter Overheating, (continued)
- Re: "Hypothetical" Datacenter Overheating Mike Hammett (Jan 18)
- Re: "Hypothetical" Datacenter Overheating Tom Beecher (Jan 18)
- Re: "Hypothetical" Datacenter Overheating Mike Hammett (Jan 18)
- Re: "Hypothetical" Datacenter Overheating Mel Beckman (Jan 15)
- Re: "Hypothetical" Datacenter Overheating Jay Hennigan (Jan 15)
- Message not available
- Re: "Hypothetical" Datacenter Overheating Jay Hennigan (Jan 15)
- Re: "Hypothetical" Datacenter Overheating Martin Hannigan (Jan 15)
- Re: "Hypothetical" Datacenter Overheating Bryan Holloway (Jan 16)
- Re: "Hypothetical" Datacenter Overheating Mel Beckman (Jan 15)
- Re: "Hypothetical" Datacenter Overheating Lamar Owen (Jan 15)
- Re: "Hypothetical" Datacenter Overheating Shane Ronan (Jan 16)
- Re: "Hypothetical" Datacenter Overheating Ray Bellis (Jan 16)
- Re: "Hypothetical" Datacenter Overheating Glenn McGurrin via NANOG (Jan 16)
- Re: "Hypothetical" Datacenter Overheating Lamar Owen (Jan 17)
- Re: "Hypothetical" Datacenter Overheating Tom Beecher (Jan 17)