On Wed, 13 Nov 2013, Roy hockett wrote:

Has anyone ever used a below grade vault for housing fiber cross connects?

We have to move a fiber interconnect facility due to the current building being demolished. If you have I would be interested in talking to you. If there are more appropriate lists, I would appreciate any suggestions.

When you say "below grade vault", do you mean something that's only accessible through a manhole?

I haven't done this specifically, however if the vault does not have a controlled environment, you could be dealing with massive headaches related to dust/dirt contamination, moisture penetration, etc. I work in a large-campus .edu environment, so I'm some of the headaches you're probably trying to avoid. Also, be aware that access to the vault could be an issue. There are OSHA regs related to what sort of training and safety equipment someone who will be working in an underground vault must have.

I'm assuming that the fiber will be cross-connected to a new location prior to the building being demolished.

Not knowing your outside plant or circumstances, would it be feasible to fusion-splice a new tail onto the fiber that was going to the building that's being demolished, or (ideally) pulling a new piece of fiber to the new building, so you don't have to deal with potentially dodgy splices?

jms