Re: LX sfp minimum range


From: Tom Storey <tom () snnap net>
Date: Sun, 29 Jan 2012 12:35:40 +0000

I once tried an LX-SMF-MMF-LX type setup using mode conditioning patch
leads between the SMF-MMF and MMF-LX portions of the span. I would be
hesitant to recommend it, simply touching the patch lead on the MMF-LX
portion would result in horrendous error counts. Suffice to say, we bit the
bullet and got some SMF blown through (tubes ftw).

I have also used LX-LX on short SMF runs of a couple of metres, for 1G and
10G, with no issues.

On 27 January 2012 16:47, Pierre-Yves Maunier <nanog () maunier org> wrote:

2012/1/27 Steven Tardy <sjt5 () its msstate edu>

On 01/26/12 16:33, Pierre-Yves Maunier wrote:



It can happends that SX works on singlemode but it can fail anytime.

just because you can doesn't mean you should.

we have experience multiple cases where LX-MMF-LX works great for 3-5+
years...
then one day no longer gets link. swapping to a different fiber pair
restores link.
can't remember SX-MMF-SX failing after years of service.


That's why I wrote 'but it can fail anytime' meaning, I strongly recommand
to NOT do it.


--
Pierre-Yves Maunier