On Dec 21, 2012, at 10:54 , George Herbert <george.herbert () gmail com> wrote:

On Thu, Dec 20, 2012 at 3:20 PM, Matthew Kaufman <matthew () matthew at> wrote:
On 12/17/2012 9:22 AM, joel jaeggli wrote:

If the facility is big enough the utility of twisted pair becomes quite
limited, both due to distance and differing electrical potential,
multibuilding campuses in particular make this is a nonstarter.


For twisted-pair Ethernet: Distance yes. Differing electrical potential no.
It is a balanced pair, transformer coupled at both ends. As long as AC
common-mode pickup doesn't saturate the transformer core, it just works.

...Up to certain limits of DC / ground differential between the ends,
at which one can cause sparks anyways.

Yes, the POTS telcos use 48V in the same or lower quality wire pairs,
and the various CatN wires should be able to take it, and the
connectors.  I'm not sure whether the sparks were from 110 or 220 V of
differential, but I saw sparks.

Sparks come from voltage, but wire tolerance is entirely a matter of amperage.

A 24ga cat-6 wire can take millions of volts as long as you keep the amperage
low enough.

Owen