Re: Want to move to all 208V for server racks
From: Kevin Day <toasty () dragondata com>
Date: Thu, 2 Dec 2010 11:51:42 -0600
On Dec 2, 2010, at 11:06 AM, Owen DeLong wrote:
It is not uncommon for three-phase panels to be different and have all three phases in the panel each phase feeding every third breaker slot.
I was just recently trying to explain this to a European friend who thought I was hallucinating this system, so I took a picture. http://dl.dropbox.com/u/230717/temp/208YPanel.jpg That's a picture of one of the breaker boxes in our office, showing what you described. There are 3 phases coming into the panel, each a different coil off a Y transformer, as well as a "neutral". Those are the 4 black wires you see at the bottom. You can see how the three hot phases are staggered as they go up the breaker rails. For standard 110V service, you use a single-wide breaker and send one hot phase + neutral and you get 110V. The difference between two phases is 208 volts though, so you use a double wide breaker and can send to device without using a neutral wire. Just 2 hots and a ground. If that's all you're doing (you don't need legacy 110V service anywhere) you skip the ground wire going into the panel entirely. -- Kevin
Current thread:
- Want to move to all 208V for server racks Jay Nakamura (Dec 02)
- Re: Want to move to all 208V for server racks William Herrin (Dec 02)
- Re: Want to move to all 208V for server racks Ingo Flaschberger (Dec 02)
- Re: Want to move to all 208V for server racks Jay Nakamura (Dec 02)
- Re: Want to move to all 208V for server racks Seth Mattinen (Dec 02)
- Re: Want to move to all 208V for server racks Ingo Flaschberger (Dec 02)
- RE: Want to move to all 208V for server racks Alex Rubenstein (Dec 02)
- Re: Want to move to all 208V for server racks Jay Ashworth (Dec 02)
- Re: Want to move to all 208V for server racks Leo Bicknell (Dec 02)
- Re: Want to move to all 208V for server racks Owen DeLong (Dec 02)
- Re: Want to move to all 208V for server racks Kevin Day (Dec 02)
- Re: Want to move to all 208V for server racks Jay Ashworth (Dec 02)
- Re: Want to move to all 208V for server racks Ingo Flaschberger (Dec 02)
- Re: Want to move to all 208V for server racks Ingo Flaschberger (Dec 02)
- Re: Want to move to all 208V for server racks Kevin Day (Dec 02)
- Re: Want to move to all 208V for server racks Ingo Flaschberger (Dec 02)
- Re: Want to move to all 208V for server racks Kevin Day (Dec 02)
- Re: Want to move to all 208V for server racks Ingo Flaschberger (Dec 02)
- Re: Want to move to all 208V for server racks Jay Ashworth (Dec 02)
- Re: Want to move to all 208V for server racks Steven Bellovin (Dec 02)
- Re: Want to move to all 208V for server racks Darren Bolding (Dec 02)
- Re: Want to move to all 208V for server racks Jay Nakamura (Dec 02)