Re: Looking for advice on datacenter electrical/generator


From: Andy Dills <andy () xecu net>
Date: Thu, 3 Apr 2003 12:42:20 -0500 (EST)


On Thu, 3 Apr 2003, Chris Adams wrote:

We have about 10-15 minutes of UPS capacity.

The important thing with a generator is to make sure you test it
regularly.  Ours (a diesel at one POP and a natural gas at another)
automatically run each week and alert us to any problems.  Then, to test
the full system (transfer switch, etc.), we "pull the handle" (shut off
utility power) once a month and make sure that everything works as it is
supposed to.

I agree about running the generator at least once a week...you need to
ensure that the startup battery stays well charged.

However, I disagree about doing a full-scale test once a month. Do that 2
or 3 times a year at most. Why? Your batteries are rated for X number of
discharges. No need to hasten their failure. As long as the generator
works, you shouldn't be worried. What are the chances your transfer switch
is going to fail?

Andy