Re: Power cut if temps are too high
From: Mel Beckman <mel () beckman org>
Date: Mon, 27 May 2019 18:20:36 +0000
We considered this approach, but we wanted to have notifications precede shut down, and give a remote support person the ability to prevent the shut down. Our SNMP based system gives us that option. -mel
On May 27, 2019, at 11:16 AM, Brian Kantor <Brian () ampr org> wrote: A simple air conditioner thermostat wired to the EPO switch. For safety, wire two thermostats in series so BOTH have to trip before power is shut off. Note that the EPO rarely does an orderly shutdown, but then this is a sort of an emergency. - BrianOn Mon, May 27, 2019 at 02:00:39PM -0400, Dovid Bender wrote: Hi, Is anyone aware of a device that will cut the power if the room goes above X degrees? I am looking for something as a just in case. Regards, Dovid
Current thread:
- Power cut if temps are too high Dovid Bender (May 27)
- Re: Power cut if temps are too high Brian Kantor (May 27)
- Re: Power cut if temps are too high Mel Beckman (May 27)
- Re: Power cut if temps are too high Wayne Bouchard (May 28)
- Re: Power cut if temps are too high Brandon Ross (May 27)
- Re: Power cut if temps are too high Brian Kantor (May 27)
- Re: Power cut if temps are too high Mel Beckman (May 27)
- Re: Power cut if temps are too high Owen DeLong (May 27)
- Re: Power cut if temps are too high Mel Beckman (May 27)
- Re: Power cut if temps are too high Brian Kantor (May 27)
- Re: Power cut if temps are too high Mel Beckman (May 27)
- Re: Power cut if temps are too high Haudy Kazemi (May 27)
- Re: Power cut if temps are too high bzs (May 28)
- Re: Power cut if temps are too high Owen DeLong (May 28)
- Re: Power cut if temps are too high bzs (May 28)
- Re: Power cut if temps are too high Haudy Kazemi (May 27)