I recently bought a UPS with a 30R plug on it, and sat and tried for about 20 minutes to plug it into what I thought 
was a 30 socket. It was, in fact, a 20. They're similar enough that if you're looking at the ends you might be 
convinced that someone has bent a one of the ends of the plug funny, but no amount of trying will make them fit.

Malcolm 

-----Original Message-----
From: Jay Ashworth [mailto:jra () baylink com] 
Sent: Tuesday, March 18, 2014 4:12 PM
To: NANOG
Subject: Re: L6-20P -> L6-30R

----- Original Message -----
From: "Randy" <amps () djlab com>

I have a situation where a 208v/20A PDU (L6-20P) is supposedly hooked 
to a 208v/30A circuit (L6-30R). Before I order the correct PDU's and 
whip cords...sanity check...are connectors 'similar' enough that this 
is possible (with force) or am I going to find we've actually got 
L6-20R's on the provider side?

As it happens, the chart at 

  http://www.stayonline.com/reference-nema-locking.aspx

suggests that the L6-20 and L6-30 are less different than you'd expect.

I *think* those are on different diameters, and a datacenter employee ought to friggin' know better... but I don't 
think it's 100% impossible that this has happened.  

If it did, you're gonna replace the plug anyway...

As long as there's a 20A breaker on the PDU, you're safe, if not within code.

Cheers,
-- jra
-- 