nanog mailing list archives

RE: OT: Below grade fiber interconnect points


From: "Sam Roche" <sroche () lakelandnetworks com>
Date: Thu, 14 Nov 2013 15:22:10 -0500

Here is a link to a Raycom Fosc that has pigtails and bulkheads in it that I'm guessing would suit your needs. We use 
them underground in vaults a various points where a pedestal doesn't make sense. You need to make sure there is proper 
drainage in the vault though....

Without knowing more about the physical facility, it's hard to know for sure what you need.

http://www.google.ca/url?sa=t&rct=j&q=&esrc=s&source=web&cd=10&ved=0CGsQFjAJ&url=http%3A%2F%2Fwww.raycom.cz%2Fdl2%3Fid_download%3D164&ei=KS-FUpm3M-PayAGMkIDQDw&usg=AFQjCNGrdt4iDKOmh6CNXG4YtwxZocBJTw&bvm=bv.56343320,d.aWc&cad=rja
 


Sam Roche - Supervisor of Network Operations - Lakeland Networks
sroche () lakelandnetworks com| Office:  705-640-0086  | Cell: 705-706-2606| www.lakelandnetworks.com



IT SOLUTIONS for BUSINESS
Fiber Optics, Wireless, DSL Network Provider; I.T. Support; Telephony Hardware and Cabling; SIP Trunks, VoIP; Server 
Hosting; Disaster Recovery Systems


"The information contained in this message is directed in confidence solely to the person(s) named above and may not be 
otherwise distributed, copied or disclosed.  The message may contain information that is privileged, proprietary and/or 
confidential and exempt from disclosure under applicable law.  If you have received this message in error, please 
notify the sender immediately advising of the error and delete the message without making a copy."


-----Original Message-----
From: Thomas [mailto:gravestl () swbell net] 
Sent: November-14-13 9:17 AM
To: Justin M. Streiner
Cc: nanog () nanog org
Subject: Re: OT: Below grade fiber interconnect points

Another option is an above ground  cabinet.  Many telecoms use them.

Thomas L Graves
Sent from my IPhone 


On Nov 13, 2013, at 8:04 PM, "Justin M. Streiner" <streiner () cluebyfour org> wrote:

On Wed, 13 Nov 2013, Roy Hockett wrote:

Thank you for comments. Let me clarify the situation.  We have a 
building that has been fiber cross connect location and is being 
demolished.  This location has about 20 fiber cable entering where we 
patch between fiber paths.  If we relocated these cross connect field 
to another building and that build is demolished we have to do this 
all over again, so the desire was to have an independent facility for 
the fiber cross connect field, but I am guessing due to esthetics the below ground vault was selected, we just 
learned of this selection and thus my query to this group to find other that have dealt with similar situations and 
if so, experience base recommendations, and things to be aware of.

If the vault has a controlled environment and access, similar to what you would find inside of a comms room, that's 
one thing.  If it's more like a typical manhole (damp, dirty, dark, possible temperature extremes, other 
utilities/hazards), then the only thing that should be in there is a water-tight splice case.  Fiber patches need to 
be in a clean environment.

Did this project provide any funds for relocation or replacement of the communications facilities that would be lost 
due to the demolition?  We've gone through this many times on our campus.

jms




Current thread: