Re: Want to move to all 208V for server racks
From: Leo Bicknell <bicknell () ufp org>
Date: Fri, 3 Dec 2010 09:42:10 -0800
In a message written on Fri, Dec 03, 2010 at 04:57:03PM +0000, Gary Buhrmaster wrote:
limits so that ones life has increased protection. A protective trip is better than the alternative.
Not always. I worked in a data center with something I thought was very, very cool. http://www.hilkar.com/highresistance.htm The concept, at a high level, is rather than tie the (service, not signal) ground back to grounding rods directly you run it through a large resistor. Now when a phase is "grounded" it runs through the resistor, allowing a small but safe current to flow. Why is this cool? Well, say you have a power strip running at 10A with a bunch of servers on it. If you took a paperclip and inserted it in an empty plug connecting hot to ground with a normal system (simulating a faulty bit of gear) the breaker would trip, all your servers would go off. If you did this with a high resistance setup the paperclip would conduct about 0.5A, maybe less. An alarm, dectecting current, at the resistor would go off to say there was a fault. Your circuit would draw 10.5 amps and everything would stay up and running. That faulty bit of gear didn't take down your entire power strip. This totally eliminates arc faults, and there isn't enough current to ground to arc. I think GFCI's are also unnecessary, as the fault can't conduct enough current to be harmful. Not there are a TON of other details to building such a system. Cost is a factor why more folks don't do it, and it takes a lot of pencil scratching by your EE types. Still, one of the coolest things I've ever seen, and I wish more data centers were built this way. -- Leo Bicknell - bicknell () ufp org - CCIE 3440 PGP keys at http://www.ufp.org/~bicknell/
Attachment:
_bin
Description:
Current thread:
- Re: Want to move to all 208V for server racks, (continued)
- Re: Want to move to all 208V for server racks Michael Loftis (Dec 04)
- Re: Want to move to all 208V for server racks Ingo Flaschberger (Dec 04)
- Re: Want to move to all 208V for server racks Kevin Oberman (Dec 04)
- Re: Want to move to all 208V for server racks Michael Painter (Dec 04)
- Re: Want to move to all 208V for server racks Lamar Owen (Dec 06)
- Re: Want to move to all 208V for server racks Gary Buhrmaster (Dec 04)
- Re: Want to move to all 208V for server racks Seth Mattinen (Dec 02)
- Re: Want to move to all 208V for server racks Gary Buhrmaster (Dec 03)
- Re: Want to move to all 208V for server racks Gary Buhrmaster (Dec 03)
- Re: Want to move to all 208V for server racks Jay Ashworth (Dec 03)
- Re: Want to move to all 208V for server racks Leo Bicknell (Dec 03)
- Re: Want to move to all 208V for server racks Ingo Flaschberger (Dec 03)
- RE: Want to move to all 208V for server racks Alex Rubenstein (Dec 03)
- Re: Want to move to all 208V for server racks Gary Buhrmaster (Dec 02)
- RE: Want to move to all 208V for server racks John van Oppen (Dec 02)
- RE: Want to move to all 208V for server racks Ingo Flaschberger (Dec 02)
- Re: Want to move to all 208V for server racks Lamar Owen (Dec 02)
- Re: Want to move to all 208V for server racks Lamar Owen (Dec 02)
- Re: Want to move to all 208V for server racks Justin M. Streiner (Dec 02)
- Re: Want to move to all 208V for server racks Seth Mattinen (Dec 02)