From: Gary Buhrmaster <gary.buhrmaster () gmail com>
Date: Thu, 2 Dec 2010 22:40:36 +0000
On Thu, Dec 2, 2010 at 22:07, Ricky Beam <jfbeam () gmail com> wrote: ...
I think they are now a violation of the NEC. And they were delisted by UL years ago. They pose a hazard as they will not react fast enough to prevent a fatal shock. (and the only one's I've ever seen were outlawed as the breaker itself was a fire hazard.)
While I do not have a copy of NFPA 70-2011 (the latest latest, released a few months ago), my reading of NFPA 70-2008 still allows GFCI breakers (NFPA 70 is the official name for NEC). Personally, I prefer to specify and use GFCI outlets (and I tend to not daisy chain) so that the the fault is next to the use (and no collateral outages occur). Of course, specific breakers may not meet the newest requirements.
Current thread:
- Re: Want to move to all 208V for server racks, (continued)
- Re: Want to move to all 208V for server racks Michael Painter (Dec 04)
- Re: Want to move to all 208V for server racks Lamar Owen (Dec 06)
- Re: Want to move to all 208V for server racks Gary Buhrmaster (Dec 04)
- Re: Want to move to all 208V for server racks Seth Mattinen (Dec 02)
- Re: Want to move to all 208V for server racks Gary Buhrmaster (Dec 03)
- Re: Want to move to all 208V for server racks Gary Buhrmaster (Dec 03)
- Re: Want to move to all 208V for server racks Jay Ashworth (Dec 03)
- Re: Want to move to all 208V for server racks Leo Bicknell (Dec 03)
- Re: Want to move to all 208V for server racks Ingo Flaschberger (Dec 03)
- RE: Want to move to all 208V for server racks Alex Rubenstein (Dec 03)
- Re: Want to move to all 208V for server racks Gary Buhrmaster (Dec 02)
- RE: Want to move to all 208V for server racks John van Oppen (Dec 02)
- RE: Want to move to all 208V for server racks Ingo Flaschberger (Dec 02)
- Re: Want to move to all 208V for server racks Lamar Owen (Dec 02)
- Re: Want to move to all 208V for server racks Lamar Owen (Dec 02)
- Re: Want to move to all 208V for server racks Justin M. Streiner (Dec 02)
- Re: Want to move to all 208V for server racks Seth Mattinen (Dec 02)