nanog mailing list archives
Re: Sheilded Cat-5E Ground Loop - Myth or Reality?
From: "Kevin Oberman" <oberman () es net>
Date: Wed, 10 Apr 2002 11:17:46 -0700
Date: Wed, 10 Apr 2002 17:43:50 +0000 (UTC) From: "Christopher K. Neitzert" <chris () neitzert com> Sender: owner-nanog () merit edu I'm in the process of managing cabling for a large install (500-ish runs) and a vendor came to me with a story about the creation of ground loops in running sheilded+gounded cat-5e in large installations. Does anyone have any experiences they would like to share regarding this?
Just follow standard rules for grounding. If the shield is connected to anything, it should only be connected at one end! This is really always true, but is especially true when there is significant physical distance involved as this can result in current flow between the grounds. This will almost certainly create a significant hum field. Due to its excellent common mode rejection, this may not be a real problem, but it always deteriorates S/N margins to some extent. There is also a REAL safety issue! Make sure that ground is NOT exposed at the un-grounded end. A potential of many volts can occur, especially in areas subject to thunder storms. None of his is specific to Cat-5e installations but is common to ALL electrical installations. R. Kevin Oberman, Network Engineer Energy Sciences Network (ESnet) Ernest O. Lawrence Berkeley National Laboratory (Berkeley Lab) E-mail: oberman () es net Phone: +1 510 486-8634
Current thread:
- Sheilded Cat-5E Ground Loop - Myth or Reality? Christopher K. Neitzert (Apr 10)
- Re: Sheilded Cat-5E Ground Loop - Myth or Reality? Kevin Oberman (Apr 10)
- Re: Sheilded Cat-5E Ground Loop - Myth or Reality? Barton F Bruce (Apr 10)
- Re: Sheilded Cat-5E Ground Loop - Myth or Reality? Kevin Oberman (Apr 10)
- Re: Sheilded Cat-5E Ground Loop - Myth or Reality? Barton F Bruce (Apr 10)
- Re: Sheilded Cat-5E Ground Loop - Myth or Reality? Kevin Oberman (Apr 10)
- Re: Sheilded Cat-5E Ground Loop - Myth or Reality? Christopher K. Neitzert (Apr 10)
- Re: Sheilded Cat-5E Ground Loop - Myth or Reality? David Lesher (Apr 10)
- Re: Sheilded Cat-5E Ground Loop - Myth or Reality? David Schwartz (Apr 10)
- Re: Sheilded Cat-5E Ground Loop - Myth or Reality? Mr. James W. Laferriere (Apr 10)
- Re: Sheilded Cat-5E Ground Loop - Myth or Reality? Barton F Bruce (Apr 10)
- Re: Sheilded Cat-5E Ground Loop - Myth or Reality? Kevin Oberman (Apr 10)