Re: 365 Datacenters Tampa AC Failure


From: Nick Olsen <nick () 141networks com>
Date: Tue, 13 Jun 2023 11:28:13 -0400

James, Any word on how redundant systems failed at the same time? Or why
the secondary was untested and not known-working?

It seems like HVAC maintenance was done by the night crew which was
quietly eliminated at some point.

On Tue, Jun 13, 2023 at 12:02 AM James Ashton <james () gitflorida com> wrote:

Hello all,
 From our side (365 Data Centers) We saw the issue start at a little after
6:30 PM yesterday. We had a component failure and we saw a rise in
temperature. We brought additional capacity online while we were working
with our vendors on getting replacement hardware.
The hardware has now been replaced and the system is back online.
This unit and others in this suite are on the block for replacement this
year as we add cooling capacity to our various spaces within the Franklin
Exchange building.

On a side note, this was not related to the issue mentioned from earlier
in the month. This was a straight component failure and replacement.

Any customers impacted can reach out to the 365 Customer Service Center
for details and documentation.

Thank you,
James Ashton
VP Network Engineering
365 Data Centers



------------------------------
*From: *"NANOG mailing list" <nanog () nanog org>
*To: *"George Herbert" <george.herbert () gmail com>
*Cc: *"NANOG mailing list" <nanog () nanog org>
*Sent: *Monday, June 12, 2023 8:03:10 PM
*Subject: *Re: 365 Datacenters Tampa AC Failure

Issue started a little after 2am, I was hard down till about 11:30am
(servers did a high temp shutdown)

On Jun 12, 2023 8:01 PM, Michael Spears <michael () spears io> wrote:

Yep there's issues over there. They had some compressors go down. Should
be getting back to normal now... Hasn't been a good month for them in
regards to cooling..

On Jun 12, 2023 7:15 PM, George Herbert <george.herbert () gmail com> wrote:

Oof.  Get ready to replace all spinning media you may have there.

-George

Sent from my iPhone

On Jun 12, 2023, at 4:06 PM, Nick Olsen <nick () 141networks com> wrote:


Just a heads up to anyone else colo'd at 365 TPA1/TAMSFLDE. Currently
seeing floor temps of ~105F as reported by equipment. Started yesterday at
~5:30PM eastern. 2nd AC failure in the last 30 days. They have not sent any
advisory notices as of yet.