On 9/2/21 02:16, Eric Germann via NANOG wrote:
15kW is 15kVA (not 1.5 kVA) at a power factor of 1.0, if the heat is all resistive.
Right! Even at a 0.8pf, 15kW is not 1.5kVA. I just didn't have the energy to get into it with him. Mark.