On 17/Mar/20 19:08, Warren Kumari wrote:


We had specified that the transfer pump be on the generator feed,
there was a schematic showing at is being on the generator feed, there
was even a breaker with a cable marked  "Transfer Pump (HP4,5)" ---
but it turned out to just be a ~3ft piece of cable stuffed into a
conduit, and not actually, you know, running all the way down to the
basement and connected to the transfer pump.

It's the things you rarely think about.

The Fukushima Daiichi nuclear power plant backup generator situation
comes to mind as well.