On 12/12/18 10:51 AM, William Herrin wrote:
The AV lab gets screwed. You're running the coax they need through the
noisy electrical riser because you didn't build dedicated comms risers
and closets. Naturally nobody checked with them so you don't yet
realize they can't do what they need to do with video over IP
equipment.

There are double-shield coax solutions for noisy risers.  The outer
shield is grounded to the conduit, while the inner shield is grounded at
the source equipment.  One has to be sure that the voltage differential
between shields is kept as low as practical, which means paying
attention to grounding for the conduit AND equipment.