nanog mailing list archives

Re: stacking pdu


From: Brandon Martin <lists.nanog () monmotha net>
Date: Fri, 29 May 2015 17:48:16 -0400

On 05/29/2015 05:29 PM, William Herrin wrote:
On Fri, May 29, 2015 at 4:32 PM, shawn wilson <ag4ve.us () gmail com> wrote:
Is there a way to stack PDUs? like, with 30A 220, we need more plugs
than power but I'd like them to communicate to make sure we don't over
power the circuit. Do any APC or Triplite systems support this?

Isn't it against the NEC and the fire code to stack power strips? We
all do it, but isn't it against code?

It sounds like he's asking for a PDU specifically intended to be used with managed expansion/stacking type modules. That would be permissible per NEC and most local fire codes as the device would be specifically listed for such usage. I've seen something like this inside blade/modular racks like IBM Flex systems, but unfortunately I don't know of any such off-the-shelf parts.

It would seem entirely reasonable to take a 30A/240V feed on a 6-30 or 14-30 type connection and break it out to numerous either C13 or 6-15/5-15 style sockets, possibly on a modular basis using some sort of proprietary power+data connections for the breakout. E.g. if you needed to mix 120V and 240V devices in a rack, you could get 5-15 and 6-15 breakouts with each individual outlet switched and maintain whole-rack metering.

Sounds like a really handy device, if one exists COTS.
--
Brandon Martin


Current thread: