RE: Why choose 120 volts?


From: "Aaron Wendel" <aaron () wholesaleinternet net>
Date: Tue, 26 May 2009 15:46:59 -0500

Our power is handed to us at 480v.  We then deliver it to the customer at whatever they need.  The nice thing about 
120v is that everything uses it.  No odd cords (as mentioned before) or expensive PDUs.

I've had a lot of people suggest that running our servers at 240v would save us money because we'd use less amps.  Last 
time I looked at my bill I was being billed by the kWh, not amp and 240v at half the amps is still the same wattage.  
I've been told this so many times though that I'm starting to doubt myself.  If anyone can present a reason for me to 
switch to 240v I'd like to hear it.

Aaron


-----Original Message-----
From: Seth Mattinen [mailto:sethm () rollernet us] 
Sent: Tuesday, May 26, 2009 2:39 PM
To: nanog () nanog org
Subject: Why choose 120 volts?

I have a pure curiosity question for the NANOG crowd here. If you run
your facility/datacenter/cage/rack on 120 volts, why?

I've been running my facility at 208 for years because I can get away
with lower amperage circuits. I'm curious about the reasons for using
high-amp 120 volt circuits to drive racks of equipment instead of
low-amp 208 or 240 volt circuits.

~Seth