nanog mailing list archives

Re: UPS and generator interaction?


From: Joel Jaeggli <joelja () darkwing uoregon edu>
Date: Mon, 29 Mar 2004 11:16:19 -0800 (PST)


On Mon, 29 Mar 2004, Mike Lewinski wrote:


Brian (nanog-list) wrote:

Does anyone know of a way to get a UPS to trigger a generator to start, and
to switch over to the generator power automatically or does this type of
thing just not exist?  

What Patrick said.

But, on a minor note that probably won't affect your Symmetra but I'm 
posting in case anyone else here can shed light on.... we had a power 
event this AM. The transfer switch did it's magic and all was good... 
Except for two new APC1400's- they failed once the batteries drained. I 
triple-checked that they were on the right panel, played with 
sensitivity, even tried daisy-chaining one off a good working 2200. 
Nothing I did would convince the two 1400s they had power. Once the 
house power was restored they came back to life and look normal. I later 
learned that two of our colo customers with APC1400s had the same 
problem :( Other models (even a couple non-essential lower-end, dumb APC 
450s and 650s) didn't blink at the generator power.

It's possible that the generatar is running to fast or slow and the 
frequency is out of range for the ups... I had this happen in Ghana, 
generator was producing 47.5hz, opened the throttle and everything was 
fine.
 
Mike


-- 
-------------------------------------------------------------------------- 
Joel Jaeggli           Unix Consulting         joelja () darkwing uoregon edu    
GPG Key Fingerprint:     5C6E 0104 BAF0 40B0 5BD3 C38B F000 35AB B67F 56B2