Re: Temp at Level 3 data centers
From: "Marshall, Quincy" <Quincy.Marshall () reged com>
Date: Thu, 12 Oct 2017 13:27:38 +0000
I have equipment in several L(3) DCs. I'd say that is generally the exception however I have two notable facilities (smaller type 3) that have troubles on occasion... reaching into the 80s as you commented. (Usually during the warm southern summer days) . I found that my getting to know the facility manager/personnel very useful. They gave staight up answers and have done what they could to assist. -------- Original message -------- From: Chuck Anderson <cra () WPI EDU> Date: 10/11/17 22:13 (GMT-05:00) To: nanog () nanog org Subject: Re: Temp at Level 3 data centers Install an air conditioner in your rack. On Wed, Oct 11, 2017 at 02:39:19PM -0500, Andrew Latham wrote:
David The issue has several components and is vendor agnostic. Set Point: The systems are specifically set at a temperature Capacity Ability: The systems can maintain a temperature Customer Desire: What you expect from sales promises. Sales Promise: What they might carefully avoid promising. I suggest you review your SLA and discuss with legal asap. You could have a document defining your question's answer already but it sits in a filing cabinet file labeled business continuity. If the set point is X then they likely would answer quickly that that is the case. If the capacity is lacking then they would likely redirect the issue. If they don't care about the customer that alone should be an indicator If a promise exists in the SLA then the ball is in your courtFrom the emails I fear that we have confirmed that this is normal. So yourquestion "Is the temperature at Level 3 Data Centers normally in the 80-90F range?" sounds like a Yes. Regardless of the situation always ask for names, titles, and ask vendors to repeat critical information like the status of cooling in a building designed to deal with cooling. Keep the vendors that do it well. On Wed, Oct 11, 2017 at 7:31 AM, David Hubbard < dhubbard () dino hostasaurus com> wrote:Curious if anyone on here colo’s equipment at a Level 3 facility and has found the temperature unacceptably warm? I’m having that experience currently, where ambient temp is in the 80’s, but they tell me that’s perfectly fine because vented tiles have been placed in front of all equipment racks. My equipment is alarming for high temps, so obviously not fine. Trying to find my way up to whomever I can complain to that’s in a position to do something about it but it seems the support staff have been told to brush questions about temp off as much as possible. Was wondering if this is a country-wide thing for them or unique to the data center I have equipment in. I have equipment in several others from different companies and most are probably 15-20 degrees cooler. Thanks, David
--------------------------------------------------------------------------------------- This email has been scanned for email related threats and delivered safely by Mimecast. For more information please visit http://www.mimecast.com ---------------------------------------------------------------------------------------
Current thread:
- Re: Temp at Level 3 data centers, (continued)
- Re: Temp at Level 3 data centers Chuck Anderson (Oct 11)
- Re: Temp at Level 3 data centers Jörg Kost (Oct 11)
- Re: Temp at Level 3 data centers William Herrin (Oct 11)
- Message not available
- Message not available
- Re: Temp at Level 3 data centers Baldur Norddahl (Oct 11)
- Re: Temp at Level 3 data centers William Herrin (Oct 11)
- Re: Temp at Level 3 data centers Keith Stokes (Oct 12)
- Re: Temp at Level 3 data centers David Hubbard (Oct 13)
- RE: Temp at Level 3 data centers Naslund, Steve (Oct 13)
- Re: Temp at Level 3 data centers Brielle Bruns (Oct 13)
- Re: Temp at Level 3 data centers Matthew Pounsett (Oct 12)