Re: rack power question
From: Sean Donelan <sean () donelan com>
Date: Sat, 22 Mar 2008 22:54:15 -0400 (EDT)
On Sat, 22 Mar 2008, Patrick Giagnocavo wrote:
Would someone pay extra for > 7KW in a rack? What would be the maximum you could ever see yourself needing in order to power all 42U ?
As you recognize, its not an engineering question; its an economic question. Notice how Google's space/power philosphy changed between leveraging other people's space/power, and now that they own their own space/power.
Existing equipment could exceed 20kW in a rack, and some folks are planning for equipment exceeding 30kW in a rack. But things get more interesting when you look at the total economics of a data center. 8kW/rack is the new "average," but that includes a lot of assumptions. If someone else is paying, I want it and more. If I'm paying for it, I discover I can get by with less.
Current thread:
- Re: rack power question, (continued)
- Re: rack power question Paul Vixie (Mar 25)
- Re: rack power question William Herrin (Mar 25)
- Re: rack power question Paul Vixie (Mar 25)
- Re: rack power question Petri Helenius (Mar 25)
- Re: rack power question Dorn Hetzel (Mar 26)
- Re: rack power question Petri Helenius (Mar 26)
- RE: rack power question John Lee (Mar 25)
- Message not available
- Re: rack power question Paul Vixie (Mar 25)
- data center loading (was:Re: rack power question) Lamar Owen (Mar 26)
- Re: data center loading (was:Re: rack power question) Robert Boyle (Mar 26)
- Re: rack power question Joe Greco (Mar 22)
- Re: rack power question david raistrick (Mar 22)
- Re: rack power question Patrick Clochesy (Mar 22)
- Re: rack power question Tony Finch (Mar 26)
- Re: rack power question Martin Hannigan (Mar 28)
- Re: rack power question Lamar Owen (Mar 24)