On Mon, 29 Mar 2004, Mike Lewinski wrote:

But, on a minor note that probably won't affect your Symmetra but I'm
posting in case anyone else here can shed light on.... we had a power
event this AM. The transfer switch did it's magic and all was good...
Except for two new APC1400's- they failed once the batteries drained. I
triple-checked that they were on the right panel, played with
sensitivity, even tried daisy-chaining one off a good working 2200.
Nothing I did would convince the two 1400s they had power. Once the
house power was restored they came back to life and look normal. I later
learned that two of our colo customers with APC1400s had the same
problem :( Other models (even a couple non-essential lower-end, dumb APC
450s and 650s) didn't blink at the generator power.

Check generator frequency.  If it has a mechanical governor, you may
need to replace it with electronic.

-- 