nanog mailing list archives

Re: UPS failure modes (was: fire at NAC)


From: Arman <arman () unitedlayer com>
Date: Thu, 29 May 2003 14:33:28 -0700


We are opening a new facility in SF and are seriously considering the idea
of by passing a large UPS (150-225KVA)altogether and relay on a generator
400-450KW with small UPSes on each rack.  A UPS failure would be limited to
a single rack, this way we could 

My personal experience with ATSes is limited and would appreciate any
feedback.

Our new facility is dual feed from two different power grids and we could
provide two independant power feeds to each rack one backed via a generator
and the other std house power.  Customer are welcome to bring their own
UPS.  (we know it takes away rack space).

FYI;  Our experience has shown that all UPSes (we have used APC, Best,
Liebert and Minute Man) have all failed within a 5 year period.  We have
over 30 APC UPSes and a ~20% failure rate.

thanks
arman

Joel Jaeggli wrote:

On Thu, 29 May 2003, Bill Woodcock wrote:


    > I had a little 2000VA rackmount Liebert UPS catch fire in 1997 and another
    > new and improved Liebert model almost catch fire about a year later.
    > What have others experienced as the failure mode(s) for their
    > UPS(s)?

We had a two-hour grid power outage here in Berkeley yesterday, during
which time our APC Symmetra 16kva fried two of its four batteries, and
went into bypass mode, which meant that the transition back from generator
to grid caused everything to reboot.  :-/

I've seen two previous APCs (both Matrixes) fry batteries...  The
batteries balloon up, and get really hot, and are too big to extract from
the chassis.  APC's solution to this is to have us take the entire UPS
offline for several days to completely dissipate the heat, and then try to
force the batteries out.  Since this seems to be an endemic problem, you'd
think they'd just design a chassis with somewhat more clearance around the
batteries so that failed ones could still be physically extracted.

gell cells suffer from an electron mobility problem relative to
traditional lead acid batteries. If you pull to much current off a stack
of them you can boil the electrolyte off in a very big hurry, but because
they're sealed they'll distent before they explode instead of just venting.

I have run a matrix 5000xr with 4 battery enclosures down to zero
under 65% load (220 minutes) without any untoward effects. in 100% load
or overload conditions without forced air cooling (we lose ours in power
outages) things could get uncomfortably warm.

                                -Bill



--
--------------------------------------------------------------------------
Joel Jaeggli          Academic User Services   joelja () darkwing uoregon edu
--    PGP Key Fingerprint: 1DE9 8FCA 51FB 4195 B42A 9C32 A30D 121E      --
  In Dr. Johnson's famous dictionary patriotism is defined as the last
  resort of the scoundrel.  With all due respect to an enlightened but
  inferior lexicographer I beg to submit that it is the first.
                            -- Ambrose Bierce, "The Devil's Dictionary"


Current thread: