Original release date: February 18, 2020

Summary

"*Note: *This Activity Alert uses the MITRE Adversarial Tactics, Techniques, and Common Knowledge (ATT&CK) framework. 
See the MITRE ATT&CK for Enterprise [ https://attack.mitre.org/matrices/enterprise/ ] and ATT&CK for Industrial Control 
Systems (ICS) [ https://collaborate.mitre.org/attackics/index.php/Main_Page ] frameworks for all referenced threat 
actor techniques and mitigations."

This Activity Alert summarizes an incident to which CISA recently responded. It is being shared publicly to promote 
awareness and encourage mitigations by asset owner operators across all critical infrastructure sectors.

The Cybersecurity and Infrastructure Security Agency (CISA) responded to a cyberattack affecting control and 
communication assets on the operational technology (OT) network of a natural gas compression facility. A cyber threat 
actor used a Spearphishing Link [T1192] [ https://attack.mitre.org/techniques/T1192/ ] to obtain initial access to the 
organizations information technology (IT) network before pivoting to its OT network. The threat actor then deployed 
commodity ransomware to Encrypt Data for Impact [T1486] [ https://attack.mitre.org/techniques/T1486/ ] on both 
networks. Specific assets experiencing a Loss of Availability [T826] [ 
https://collaborate.mitre.org/attackics/index.php/Technique/T826 ] on the OT network included human machine interfaces 
(HMIs), data historians, and polling servers. Impacted assets were no longer able to read and aggregate real-time 
operational data reported from low-level OT devices, resulting in a partial Loss of View [T829] [ 
https://collaborate.mitre.org/attackics/index.php/Technique/T829 ] for human operators. The attack did not impact any 
programmable logic controllers (PLCs) and at no point did the victim lose control of operations. Although the victims 
emergency response plan did not specifically consider cyberattacks, the decision was made to implement a deliberate and 
controlled shutdown to operations. This lasted approximately two days, resulting in a Loss of Productivity and Revenue 
[T828] [ https://collaborate.mitre.org/attackics/index.php/Technique/T828 ], after which normal operations resumed. 
CISA is providing this Alert to help administrators and network defenders protect their organizations against this and 
similar ransomware attacks.

Technical Details

Network and Assets

  * The victim failed to implement robust segmentation between the IT and OT networks, which allowed the adversary to 
traverse the IT-OT boundary and disable assets on both networks. 
  * The threat actor used commodity ransomware to compromise Windows-based assets on both the IT and OT networks. 
Assets impacted on the organizations OT network included HMIs, data historians, and polling servers. 
  * Because the attack was limited to Windows-based systems, PLCs responsible for directly reading and manipulating 
physical processes at the facility were not impacted. 
  * The victim was able to obtain replacement equipment and load last-known-good configurations to facilitate the 
recovery process. 
  * All OT assets directly impacted by the attack were limited to a single geographic facility. 

Planning and Operations

  * At no time did the threat actor obtain the ability to control or manipulate operations. The victim took HMIs that 
read and control operations at the facility offline. A separate and geographically distinct central control office was 
able to maintain visibility but was not instrumented for control of operations. 
  * The victims existing emergency response plan focused on threats to physical safety and not cyber incidents. 
Although the plan called for a full emergency declaration and immediate shutdown, the victim judged the operational 
impact of the incident as less severe than those anticipated by the plan and decided to implement limited emergency 
response measures. These included a four-hour transition from operational to shutdown mode combined with increased 
physical security. 
  * Although the direct operational impact of the cyberattack was limited to one control facility, geographically 
distinct compression facilities also had to halt operations because of pipeline transmission dependencies. This 
resulted in an operational shutdown of the entire pipeline asset lasting approximately two days. 
  * Although they considered a range of physical emergency scenarios, the victims emergency response plan did not 
specifically consider the risk posed by cyberattacks. Consequently, emergency response exercises also failed to provide 
employees with decision-making experience in dealing with cyberattacks. 
  * The victim cited gaps in cybersecurity knowledge and the wide range of possible scenarios as reasons for failing to 
adequately incorporate cybersecurity into emergency response planning. 

Mitigations

Asset owner operators across all sectors are encouraged to consider the following mitigations using a risk-based 
assessment strategy.

Planning and Operational Mitigations

  * Ensure the organizations emergency response plan considers the full range of potential impacts that cyberattacks 
pose to operations, including loss or manipulation of view, loss or manipulation of control, and loss of safety. In 
particular, response playbooks should identify criteria to distinguish between events requiring deliberate operational 
shutdown versus low-risk events that allow for operations to continue. 
  * Exercise the ability to fail over to alternate control systems, including manual operation while assuming degraded 
electronic communications. Capture lessons learned in emergency response playbooks. 
  * Allow employees to gain decision-making experience via tabletop exercises that incorporate loss of visibility and 
control scenarios. Capture lessons learned in emergency response playbooks. 
  * Identify single points of failure (technical and human) for operational visibility. Develop and test emergency 
response playbooks to ensure there are redundant channels that allow visibility into operations when one channel is 
compromised. 
  * Implement redundant communication capabilities between geographically separated facilities responsible for the 
operation of a single pipeline asset. Coordinate planning activities across all such facilities. 
  * Recognize the physical risks that cyberattacks pose to safety and integrate cybersecurity into the organizations 
safety training program. 
  * Ensure the organizations security program and emergency response plan consider third parties with legitimate need 
for OT network access, including engineers and vendors. 

Technical and Architectural Mitigations

  * Implement and ensure robust Network Segmentation [M1030] [ https://attack.mitre.org/mitigations/M1030/ ] between IT 
and OT networks to limit the ability of adversaries to pivot to the OT network even if the IT network is compromised. 
Define a demilitarized zone (DMZ) that eliminates unregulated communication between the IT and OT networks. 
  * Organize OT assets into logical zones by taking into account criticality, consequence, and operational necessity. 
Define acceptable communication conduits between the zones and deploy security controls to Filter Network Traffic 
[M1037] [ https://attack.mitre.org/mitigations/M1037/ ] and monitor communications between zones. Prohibit Industrial 
Control System (ICS) protocols from traversing the IT network. 
  * Require Multi-Factor Authentication [M1032] [ https://attack.mitre.org/mitigations/M1032/ ] to remotely access the 
OT and IT networks from external sources. 
  * Implement regular Data Backup [M1053] [ https://attack.mitre.org/mitigations/M1053/ ] procedures on both the IT and 
OT networks. Ensure that backups are regularly tested and isolated from network connections that could enable the 
spread of ransomware. 
  * Ensure user and process accounts are limited through Account Use Policies [M1036] [ 
https://attack.mitre.org/mitigations/M1036/ ], User Account Control [M1052] [ 
https://attack.mitre.org/mitigations/M1052/ ], and Privileged Account Management [M1026] [ 
https://attack.mitre.org/mitigations/M1026/ ]. Organize access rights based on the principles of least privilege and 
separation of duties. 
  * Enable strong spam filters to prevent phishing emails from reaching end users. Implement a User Training [M1017] [ 
https://attack.mitre.org/mitigations/M1017/ ] program to discourage users from visiting malicious websites or opening 
malicious attachments. Filter emails containing executable files from reaching end users. 
  * Filter Network Traffic [M1037] [ https://attack.mitre.org/mitigations/M1037/ ] to prohibit ingress and egress 
communications with known malicious Internet Protocol (IP) addresses. Prevent users from accessing malicious websites 
using Uniform Resource Locator (URL) blacklists and/or whitelists. 
  * Update Software [M1051] [ https://attack.mitre.org/mitigations/M1051/ ], including operating systems, applications, 
and firmware on IT network assets. Use a risk-based assessment strategy to determine which OT network assets and zones 
should participate in the patch management program. Consider using a centralized patch management system. 
  * Set Anti-virus/Anti-malware [M1049] [ https://attack.mitre.org/mitigations/M1049/ ] programs to conduct regular 
scans of IT network assets using up-to-date signatures. Use a risk-based asset inventory strategy to determine how OT 
network assets are identified and evaluated for the presence of malware.  
  * Implement Execution Prevention [M1038] [ https://attack.mitre.org/mitigations/M1038/ ] by disabling macro scripts 
from Microsoft Office files transmitted via email. Consider using Office Viewer software to open Microsoft Office files 
transmitted via email instead of full Microsoft Office suite applications. 
  * Implement Execution Prevention [M1038] [ https://attack.mitre.org/mitigations/M1038/ ] via application 
whitelisting, which only allows systems to execute programs known and permitted by security policy. Implement software 
restriction policies (SRPs) or other controls to prevent programs from executing from common ransomware locations, such 
as temporary folders supporting popular internet browsers or compression/decompression programs, including the 
AppData/LocalAppData folder. 
  * Limit Access to Resources over Network [M1035] [ https://attack.mitre.org/mitigations/M1035/ ], especially by 
restricting Remote Desktop Protocol (RDP). If after assessing risks RDP is deemed operationally necessary, restrict the 
originating sources and require Multi-Factor Authentication [M1032] [ https://attack.mitre.org/mitigations/M1032/ ]. 

Resources

  * CISA Ransomware One-Pager and Technical Document [ 
https://www.us-cert.gov/sites/default/files/publications/Ransomware_Executive_One-Pager_and_Technical_Document-FINAL.pdf
 ] (CISA, 2019) 
  * CISA Insights: Ransomware Outbreak [ 
https://www.us-cert.gov/sites/default/files/2019-08/CISA_Insights-Ransomware_Outbreak_S508C.pdf ] (CISA, 2019) 
  * Pipeline Cybersecurity Initiative [ https://www.cisa.gov/pipeline-cybersecurity-initiative ] (CISA, 2018) 
  * CISA Webinar: Combating Ransomware [ https://www.youtube.com/watch?v=D8kC07tu27A ] (CISA, 2018) 
  * Framework for Improving Critical Infrastructure Cybersecurity [ 
https://nvlpubs.nist.gov/nistpubs/CSWP/NIST.CSWP.04162018.pdf ] (NIST, 2018) 
  * Data Integrity: Identifying and Protecting Assets Against Ransomware and Other Destructive Events [ 
https://csrc.nist.gov/publications/detail/white-paper/2018/02/07/data-integrity-identifying-and-protecting-assets-vs-ransomware/final
 ] (NIST, 2018) 
  * Data Integrity: Detecting and Responding to Ransomware and Other Destructive Events [ 
https://csrc.nist.gov/publications/detail/white-paper/2018/02/07/data-integrity-detecting-and-responding-to-ransomware/final
 ] (NIST, 2018) 
  * Pipeline Security Guidelines [ https://www.tsa.gov/sites/default/files/pipeline_security_guidelines.pdf ] (TSA, 
2018) 
  * NIST SP 800-11: Data Integrity: Recovering from Ransomware and Other Destructive Events [ 
https://csrc.nist.gov/publications/detail/sp/1800-11/draft ] (NIST, 2017) 
  * Guide to Industrial Control Systems (ICS) Security [ 
https://csrc.nist.gov/publications/detail/sp/800-82/rev-2/final ] (NIST, 2015) 
  * Oil and Natural Gas Subsector Cybersecurity Capability Maturity Model [ 
https://www.energy.gov/sites/prod/files/2014/03/f13/ONG-C2M2-v1-1_cor.pdf ] (DOE, 2014) 

Revisions

  * February 18, 2020: Initial Version 
________________________________________________________________________

This product is provided subject to this Notification [ https://www.us-cert.gov/privacy/notification ] and this Privacy 
& Use [ https://www.dhs.gov/privacy-policy ] policy.

body { font-size: 1em; font-family: Arial, Verdana, sans-serif; font-weight: normal; font-style: normal; color: 
#333333; } ________________________________________________________________________

A copy of this publication is available at www.us-cert.gov [ https://www.us-cert.gov ]. If you need help or have 
questions, please send an email to info () us-cert gov. Do not reply to this message since this email was sent from a 
notification-only address that is not monitored. To ensure you receive future US-CERT products, please add US-CERT () 
ncas us-cert gov to your address book. 

OTHER RESOURCES: Contact Us [ http://www.us-cert.gov/contact-us/ ] | Security Publications [ 
http://www.us-cert.gov/security-publications ] | Alerts and Tips [ http://www.us-cert.gov/ncas ] | Related Resources [ 
http://www.us-cert.gov/related-resources ]  

STAY CONNECTED: Sign up for email updates [ http://public.govdelivery.com/accounts/USDHSUSCERT/subscriber/new ] 


Current thread: